TeSys Deca contactor, 3 poles (3NO), for motor control applications up to 150A/1000V AC-3 (75kW@400V) , power connection by screw connectors 2 inputs, control connection by screw clamp terminals , it procures high reliability and durability.
Technical Data
- [Ue] rated operational voltage : Power circuit: <= 1000 V AC 25...400 Hz
- Power circuit: <= 300 V DC
- [Ie] rated operational current : 200 A (at <60 C) at <= 440 V AC AC-1 for power circuit
- 150 A (at <60 C) at <= 440 V AC AC-3 for power circuit
- 150 A (at <60 C) at <= 440 V AC AC-3e for power circuit
- [Uc] control circuit voltage : 24 V DC
- Motor power kW : 40 kW at 220…230 V AC 50/60 Hz (AC-3)
- 75 kW at 380…400 V AC 50/60 Hz (AC-3)
- 80 kW at 415…440 V AC 50/60 Hz (AC-3)
- 90 kW at 500 V AC 50/60 Hz (AC-3)
- 100 kW at 660…690 V AC 50/60 Hz (AC-3)
- 75 kW at 1000 V AC 50/60 Hz (AC-3)
- 22 kW at 400 V AC 50/60 Hz (AC-4)
- 40 kW at 220…230 V AC 50/60 Hz (AC-3e)
- 75 kW at 380…400 V AC 50/60 Hz (AC-3e)
- 80 kW at 415…440 V AC 50/60 Hz (AC-3e)
- 90 kW at 500 V AC 50/60 Hz (AC-3e)
- 100 kW at 660…690 V AC 50/60 Hz (AC-3e)
- 75 kW at 1000 V AC 50/60 Hz (AC-3e)
- Motor power hp : 40 hp at 200/208 V AC 50/60 Hz for 3 phases motors
- 50 hp at 230/240 V AC 50/60 Hz for 3 phases motors
- 100 hp at 460/480 V AC 50/60 Hz for 3 phases motors
- 125 hp at 575/600 V AC 50/60 Hz for 3 phases motors
- Pole contact composition : 3 NO
- [Ith] conventional free air thermal current : 200 A (at 60 C) for power circuit
- Irms rated making capacity : 140 A AC for signalling circuit conforming to IEC 60947-5-1
- 250 A DC for signaling circuit conforming to IEC 60947-5-1
- 1660 A at 440 V for power circuit conforming to IEC 60947
- Rated breaking capacity : 1400 A at 440 V for power circuit conforming to IEC 60947
- Power dissipation per pole : 24 W AC-1
- 13.5 W AC-3
- 13.5 W AC-3e
- [Uimp] rated impulse withstand voltage : 8 kV conforming to IEC 60947
- Mechanical durability : 8 Mcycles
- Electrical durability : 0.85 Mcycles 150 A AC-3 at Ue <= 440 V
- 1 Mcycles 200 A AC-1 at Ue <= 440 V
- 0.85 Mcycles 150 A AC-3e at Ue <= 440 V
- Control circuit voltage limits : 0.75…1.2 Uc (-4055 C):operational DC
- 0.15…0.4 Uc (-4070 C):drop-out DC
- 1…1.2 Uc (5570 C):operational DC
- Inrush power in W : 270365 W (at 20 C)
- Hold-in power consumption in W :2.45.1 W at 20 C
- Operating time : 20…35 ms closing
- 40…75 ms opening
- Time constant : 25 ms
- Maximum operating rate : 1200 cyc/h 60 C
- Permissible ambient air temperature around the device : -4060 C
- 6070 C with derating
- Fire resistance : 850 C conforming to IEC 60695-2-1
- Height : 158 mm
- Width : 120 mm
- Depth : 136 mm
- Net weight : 2.5 kg