About The Product
TeSys D contactors have been designed for perfect integration into control systems. They can be used to create motor starters for almost any type of application. TeSys D contactors are available in 13 contactor ratings for inductive motor applications up to 150 full-load amps and resistive loads up to 200 amps. This 40A inductive 3 pole IEC contactor can be mounted on DIN rail or mounted directly to a panel. Contactors have both Horsepower and Kw motor rating for international acceptance.
Technical Data
- [Ue] rated operational voltage : Power circuit <= 690 V AC 25...400 Hz
- Power circuit <= 300 V DC
- [Ie] rated operational current : 60 A 140 F (60 C)) <= 440 V AC AC-1 power circuit
- 40 A 140 F (60 C)) <= 440 V AC AC-3 power circuit
- 40 A 140 F (60 C)) <= 440 V AC AC-3e power circuit
- [Uc] control circuit voltage : 24 V DC
- Motor power kW : 18.5 kW 380…400 V AC 50/60 Hz AC-3)
- 11 kW 220…230 V AC 50/60 Hz AC-3)
- 22 kW 415…440 V AC 50/60 Hz AC-3)
- 22 kW 500 V AC 50/60 Hz AC-3)
- 30 kW 660…690 V AC 50/60 Hz AC-3)
- 9 kW 400 V AC 50/60 Hz AC-4)
- 18.5 kW 380…400 V AC 50/60 Hz AC-3e)
- 11 kW 220…230 V AC 50/60 Hz AC-3e)
- 22 kW 415…440 V AC 50/60 Hz AC-3e)
- 22 kW 500 V AC 50/60 Hz AC-3e)
- 30 kW 660…690 V AC 50/60 Hz AC-3e)
- Maximum Horse Power Rating : 5 hp 230/240 V at AC 50/60 Hz for 1 phase
- 10 hp 230/240 V at AC 50/60 Hz for 3 phase
- 30 hp 575/600 V at AC 50/60 Hz for 3 phase
- 10 hp 200/208 V at AC 50/60 Hz for 3 phase
- 3 hp 115 V at AC 50/60 Hz for 1 phase
- 30 hp 460/480 V at AC 50/60 Hz for 3 phase
- [Ith] conventional free air thermal current : 10 A 140 F (60 C) signalling circuit
- 60 A 140 F (60 C) power circuit
- Irms rated making capacity : 140 A AC signalling circuit IEC 60947-5-1
- 250 A DC signalling circuit IEC 60947-5-1
- 800 A 440 V power circuit IEC 60947
- Rated breaking capacity : 800 A 440 V power circuit IEC 60947
- Average impedance : 1.5 mOhm – Ith 60 A 50 Hz power circuit
- Power dissipation per pole : 2.4 W AC-3
- 5.4 W AC-1
- 2.4 W AC-3e
- [Ui] rated insulation voltage : Power circuit 600 V CSA
- Power circuit 600 V UL
- Signalling circuit 690 V IEC 60947-1
- Signalling circuit 600 V CSA
- Signalling circuit 600 V UL
- Power circuit 690 V IEC 60947-4-1
- Safety reliability level : B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1
- B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
- Mechanical durability : 10 Mcycles
- Electrical durability : 0.7 Mcycles 60 A AC-1 <= 440 V
- 1.5 Mcycles 40 A AC-3 <= 440 V
- 1.5 Mcycles 40 A AC-3e <= 440 V
- Control circuit voltage limits : 0.1…0.3 Uc -40158 F (-4070 C) drop-out DC
- 0.75…1.25 Uc -40140 F (-4060 C) operational DC
- 1…1.25 Uc 140158 F (6070 C) operational DC
- Inrush power in W : 19 W 68 F (20 C))
- Hold-in power consumption in W : 7.4 W 68 F (20 C)
- Operating time : 42.5…57.5 ms closing
- 16…24 ms opening
- Time constant : 34 ms
- Maximum operating rate : 3600 cyc/h 140 F (60 C)
- Height : 122 mm
- Width : 55 mm
- Depth : 120 mm
- Net Weight : 0.925 kg
Reviews